Page 16 - Fan Coil Unit
P. 16

FAN COIL UNIT / AIR CONDITIONING




               485 Communication Central Control (RS-485)




               This is a communication method that uses a 2-wire, half-duplex, multi-point serial connection.
               It is a communication method where the main control unit sends and receives commands to and
               from each device by varying the transmission and reception times. In this method, all devices are
               connected in series for communication.
               (Master/Slave Method)







                >> Features of 485 Communication

                 01                               02                              03




                 Allows for multi-drop            Capable of transmitting up to    The optimal choice for serial
                 communication, enabling up to    1.2 km at 100 kbps              communication in environments
                 32 transmit/receive units.                                       with distributed equipment across
                                                                                  multiple networks, dealing with
                 04                               05                              noise and using numerous devices



                 The 2-wire system allows for     When connecting more than
                 construction at a lower cost than   32 products, a separate MCU is
                 other wired systems.             required, and the MCU also has
                                                  32 communication points.

                    Comparison of Communication Methods

                  Item           RS-485                                 PLC (Power Line Communication)
                  Communication                                          Power lines used for communication
                  Method          Dedicated communication cable          High-speed power line Ethernet communication
                                  1.2 km per device                      300 m per device
                  Signal Reach
                                  Communication speed decreases depending on distance  Decreases due to the reduced power signal
                  Communication Line
                  Construction    Requires dedicated cable line construction  No line construction required due to use of power lines
                  Communication   9600-38,400 bps                        Physical speed 200 Mbps
                  Speed                                                  Typically 40-80 Mbps
                                  Limited control
                                  Up to 32 devices per master
                  Control Quantity                                       Up to 25,600 devices for a single network
                                  For more than 32 devices, MCU is needed
                                  Up to 32 devices per MCU
                  Signal Converter  RS-232 – RS-485 conversion           No separate converter required
                                                                         Communication PCB by product
                                  Communication PCB by product           3-phase power line communication modem
                  Installation    MCU installation by zones (24-32 units)  3-phase/single-phase power line coupler
                  Equipment       RS-485 or Ethernet communication between MCUs  Blocking filter
                                                                         Signal amplifier (installed depending on field conditions)
                                  Potential issues when controlling large quantities   PC control available
                  Individual Operating   depending on the communication speed due to FCU quantity and   Use of high-speed Ethernet communication
                  Status
                                  distance                               Individual control and monitoring available
                                  Up to 16 device connections            Up to 32 device connections
                  Wired Remote Control
                                  Master (1 EA) + Slave (15 EA)          Master (1 EA) + Slave (15 EA)
                  Wired Remote Control   4-wire power and communication line  2-wire power supply using communication line
                  Connection
                                  Line work required when changing the office structure  When changing the office layout, it only requires setting the IP
                  Structural Change  Adjust the FCU ID for each product by adjusting the ADD switch on   by group or product
                                  the PCB installed on the product
                                  New construction buildings: Piping work taking into account   No separate communication line work required
                                  communication line work is required
                  Features                                               Network equipment related to communication must be
                                  Existing buildings: Many obstacles exist when installing   installed on the FCU power line
                                  communication lines.