Page 43 - Fan Coil Unit
P. 43
1-Way Ceiling Cassette Type
840 (Hanger Posi�on)
1 8 3 5 6
820 (Ceiling Hole Dimensions) Ceiling Cassette Type
525 (Ceiling Hole Dimensions) 415 (Hanger Posi�on) Inspec�on
Hole
7 2 4
Concealed Type
9 12
Ceiling
Surface
10 11
Part No DESCRIPTION MAT’L Q’TY REMARK Part No DESCRIPTION MAT’L Q’TY REMARK
1 INTERIOR GRILLE ASS'Y ABS/HIPS 1 7 HANGING BRACKET GI 4
2 GRILLE REMOVAL BUTTON ABS/HIPS 2 SLIDING TYPE 8 REMOTE CONTROL RECEIVER ACRYLIC 1
3 NAME PLATE 1 9 DRAIN PIPE PORT 1 Ø16 (Outer Diameter)
4 RETURN GRILLE ABS/HIPS 1 10 DRAIN PUMP ASS’Y 1 1Ø, 220 V, 60 Hz Floor-Stand Type
5 FLAP ABS/HIPS 4 11 WATER OUTLET BS 1 PF 3/4" (20 A)
6 STEPPING MOTOR ASS'Y 1 DC 12 V 12 WATER INLET BS 1 PF 3/4" (20 A)
Standard Specifications
Category Specifications SFC1-1.5KB SFC1-2KB SFC1-2.5KB SFC1-3KB SFC1-3.5KB
Capacity Conditions A B A B A B A B A B
Cooling W 2,450 1,860 3,210 2,440 3,840 2,910 4,730 3,610 5,360 4,070
Capacity Kcal/h 2,110 1,600 2,760 2,100 3,300 2,500 4,070 3,100 4,610 3,500
Capacity Heating W 4,880 2,980 6,070 3,720 7,070 4,300 8,520 5,230 10,070 6,160
Capacity Kcal/h 4,200 2,560 5,220 3,200 6,080 3,700 7,330 4,500 8,660 5,300
Flow Rate ℓ/min 7.1 5.3 9.3 7.0 11.1 8.3 13.6 10.3 15.4 11.7 Stand Type
Head Loss mAq 0.58 0.32 1 0.57 1.42 0.79 3.2 1.84 4.1 2.37
Type Double Suction SIROCCO Type
SIZE mm Ø140 X 165 Ø140 X 200 Ø140 X 200 Ø140 X 200 Ø140 X 200
Fan Blower Airflow Volume m /min 5.6 7 9 9 11
3
Drive Type Direct Drive Motor
Quantity EA 1
Type BLDC Semi-Enclosed Type (8 poles, Class E insulation)
Motor
Quantity EA 1
Power Consumption W 30 41 74 74 108
Heat Exchanger Type Integrated Multi-Pass Cross Finned Tube (Slit Fin)
Inlet A PF 3/4" (20 A)
Pipe Outlet A PF 3/4" (20 A)
Drain Ø16 (Outer Diameter) / Built-in Drain Pump (10 W) / Head 600 mm
External Material Main Body: Zinc-Coated Steel Plate (0.8 t, 1.0 t) / Grille Panel: Injection Molded (HIPS, ABS Material)
Air Volume Control Turbo, Strong, Medium, Weak, Automatic Wireless Remote Controller (Wired remote controller is optional)
Power Supply Single Phase 220 V 60 HZ Facility Cultivation Type
AIR FILTER Vinyl Chloride (Submersible Type)
Discharge Swing Motor DC 12 V, STEPPING MOTOR
Main Body D x W x H 490 X 780 X 231
Dimensions
Panel (mm) 850 X 575 X 35
Product Weight Kg 27 27 28 30 30
(Note) 1. Capacity Condition A: Cooling Capacity: When indoor air is DB 27°C, WB 21°C, and inlet water temperature is 5°C Heating Capacity: When indoor air is 18°C, and inlet water temperature is 80°C
2. Capacity Condition B: Cooling Capacity: When indoor air is DB 27°C, WB 19.5°C, and inlet water temperature is 7°C Heating Capacity: When indoor air is 21°C, and inlet water temperature is 60°C
43