Page 29 - Energy Recovery Ventilation
P. 29
Ductless
Heat Recovery Ventilation Unit | Large-Capacity
L PART
A
NO. PART NAME MAT'L Q'TY DESCRIPTION
1 CASING SGCC 1 - Slim
8 2 ACCESS DOOR SGCC 1 -
3 FAN & MOTOR - 2 BLDC MOTOR
OA RA 4 HEAT EXCHANGER PULP 1 SET Special Processed Pulp for
Heat Exchange
5 PRE-FILTER - 2 SETS Nonwoven Fabric
D W B 6 DUCT FLANGE - 2 F (SA,RA)
7 MD - 1 F (EA) Small
EA SA 8 BDD - 1 F (OA)
9 CONTROL BOX SGCC 1 PCB Included
7
DIMENSIONS
MODEL W L H A B D F
SW-1500SBa 1,125 1,200 545 900 1,167 500 Ø300
Inspec�on Hole Standard
600 × 600 SW-2000SBa 1,500 1,400 545 900 1,542 700 Ø350
3 2 5 4 1 6
ABS
H
9
Standard Specifications
Classification Unit SW-1500SBa SW-2000SBa ABS/BYPASS
Strong Medium Weak Strong Medium Weak
Airflow Volume CMH
1,500 1,500 1,125 2,000 2,000 1,750
Power Consumption W 1,050 696 530 1,150 927 910
Static Pressure mmAq 15 12 15 12
Product Size (W × L × H) mm 1,125 × 1,200 × 545 1,500 × 1,400 × 545
Duct Diameter mm (Ø) 300 350
Noise* dB 60dB (A) or less
Power Supply - Ø1 / 220 V / 60 Hz Large Capacity
Heat Recovery Rate % More than 70% when heating
Heat Exchanger - Square Plate Heat Exchanger
Air Volume Control Method - ON/OFF, 3-Stage Control
Filter - PRE FILTER
Casing - Galvanized Steel Sheet, Color-Coated Steel Sheet (optional)
Exhaust Unit
Optional Specifications - MEDIUM FILTER, Antibacterial, Deodorization, Copper Sulfate, HEPA Filter, Photocatalyst Unit
* The noise level indication is based on the installation and completion of finishing work on-site.
29 ENERGY RECOVERY VENTILATION