Page 27 - Fan Coil Unit
P. 27
1-Way Ceiling Cassette, Slim Type, High Capacity 1-Way Slim Type Grille Panel with Inspection Hole
Korean Patent Registration Number (Utility Model) No. 10-11472719
1110 (Ceiling Hole Dimensions)
1000 (Hanger Posi�on) Korean Patent Registration Number (Design) No. 30-0777206
440 (Ceiling Hole Dimensions) 330 (Hanger Posi�on) ▶ With the integration of the grille panel and inspection hole, there is no need Ceiling Cassette Type
to install a separate inspection hole on the ceiling.
▶ Installation of inspection holes can be omitted, reducing construction costs.
▶ With no inspection openings on the ceiling surface, a seamless and integrated
interior design is achievable.
▶ Allows for convenient inspection of piping and valves.
8
10 11 7
Ceiling
Surface 13 12 6
1 4
Concealed Type
Inspec�on
Hole
9 3 5 2
Part No DESCRIPTION MAT'L Q'TY REMARK
1 INTERIOR GRILLE ASS'Y ABS/HIPS 1
2 GRILLE REMOVAL BUTTON ABS/HIPS 2 SLIDING TYPE
3 NAME PLATE 1
4 RETURN GRILLE ABS/HIPS 1
5 FLAP ABS/HIPS 4
6 STEPPING MOTOR ASS'Y 1 DC 12 V Floor-Stand Type
7 MOTOR 1 BLDC
8 HANGING BRACKET ABS 4
9 REMOTE CONTROL RECEIVER ACRYLIC 1
10 DRAIN PIPE PORT 1 Ø16 (Outer Diameter)
11 DRAIN PUMP ASS’Y 1 1Ø, 220 V, 60 Hz
12 WATER OUTLET BS 1 PF 3/4" (20 A)
13 WATER INLET BS 1 PF 3/4" (20 A)
Standard Specifications
Category Specifications SFC-S4KH SFC-S4.5KH
Capacity Conditions A B A B
W 6,130 4,650 6,920 5,230 Stand Type
Cooling Capacity
kcal/h 5,270 4,000 5,950 4,500
Capacity W 13,270 8,140 14,300 8,740
Heating Capacity
kcal/h 11,410 7,000 12,300 7,520
Flow Rate ℓ/min 17.5 13.5 19.8 15.0
Head Loss mAq 3.1 1.8 3.9 2.3
Type CROSS FLOW FAN
Fan Blower
Airflow Volume m /min 13.5 15
3
Type BLDC
Motor
Quantity EA 1
Power Consumption W 67 83
Heat Exchanger Type Integrated Multi-Pass Cross Finned Tube (Slit Fin)
Inlet mm 20A
Pipe Outlet mm 20A
Drain mm 16A
Power Supply Single Phase 220 V 60 HZ Facility Cultivation Type
Communication Line Shield cable AWG24 x 4C
AIR FILTER Vinyl Chloride (Submersible Type)
Exterior Main Body D x W x H (mm) 430x950x170
Dimensions Panel 490x1,160x40
Product Weight kg 22
(Note) 1. Capacity Condition A: Cooling Capacity: When indoor air is DB 27°C, WB 21°C, and inlet water temperature is 5°C Heating Capacity: When indoor air is 18°C, and inlet water temperature is 80°C
2. Capacity Condition B: Cooling Capacity: When indoor air is DB 27°C, WB 19.5°C, and inlet water temperature is 7°C Heating Capacity: When indoor air is 21°C, and inlet water temperature is 60°C
27