Page 29 - Fan Coil Unit
P. 29
1-Way EPP Ceiling Cassette, Slim Type 1-Way Slim Type Grille Panel with Inspection Hole
Korean Patent Registration Number (Utility Model) No. 10-11472719
1110 (Ceiling Hole Dimensions)
Korean Patent Registration Number (Design) No. 30-0777206
1010 (Hanger Posi�on)
▶ With the integration of the grille panel and inspection hole, there is no need
450 (Ceiling Hole Dimensions) 330 (Hanger Posi�on) ▶ Installation of inspection holes can be omitted, reducing construction costs. Ceiling Cassette Type
to install a separate inspection hole on the ceiling.
▶ With no inspection openings on the ceiling surface, a seamless and integrated
interior design is achievable.
▶ Allows for convenient inspection of piping and valves.
8
10 11 7
Ceiling
Surface 12 13 6
Concealed Type
1 4
Inspec�on
Hole
9 3 5 2
Part No DESCRIPTION MAT'L Q'TY REMARK
1 INTERIOR GRILLE ASS'Y ABS/HIPS 1
2 GRILLE REMOVAL BUTTON ABS/HIPS 2 SLIDING TYPE
3 NAME PLATE 1
4 RETURN GRILLE ABS/HIPS 1
5 FLAP ABS/HIPS 4
6 STEPPING MOTOR ASS'Y 1 DC 12 V Floor-Stand Type
7 MOTOR 1 BLDC
8 HANGING BRACKET EPP 4
9 REMOTE CONTROL RECEIVER ACRYLIC 1
10 DRAIN PIPE PORT 1 Ø16 (Outer Diameter)
11 DRAIN PUMP ASS’Y 1 1Ø, 220 V, 60 Hz
12 WATER OUTLET BS 1 PF 3/4" (20 A)
13 WATER INLET BS 1 PF 3/4" (20 A)
Standard Specifications
Category Specifications SFC-ES2.5K SFC-ES3K SFC-ES3.5K
Capacity Conditions A B A B A B
Cooling W 4,110 3,130 4,690 3,550 5,500 4,130 Stand Type
Capacity kcal/h 3,530 2,690 4,030 3,060 4,730 3,560
Capacity Heating W 7,370 4,550 9,090 5,580 11,200 6,800
Capacity kcal/h 6,340 3,910 7,820 4,800 9,630 5,850
Flow Rate ℓ/min 11.8 9.0 13.5 10.2 15.8 11.9
Head Loss mAq 2.6 1.51 3.4 1.94 4.66 2.64
Type Centrifugal Multi-Flow (Cross Flow Fan)
Fan Blower
Airflow Volume m /min 7 9 12.5
3
Type BLDC
Motor
Quantity EA 1
Power Consumption W 28 30.8 68
Heat Exchanger Type Integrated Multi-Pass Cross Finned Tube (Slit Fin)
Inlet mm 20 A
Pipe Outlet mm 20 A
Drain mm 16 A
Power Supply Single Phase 220 V 60 Hz Facility Cultivation Type
Communication Line Shield cable AWG24 x 4C
AIR FILTER Vinyl Chloride Filter
Exterior Main Body D x W x H (mm) 410 x 950 x 145
Dimensions Panel 490 x1160 x 30
Product Weight kg 12
(Note) 1. Capacity Condition A: Cooling Capacity: When indoor air is DB 27°C, WB 21°C, and inlet water temperature is 5°C Heating Capacity: When indoor air is 18°C, and inlet water temperature is 80°C
2. Capacity Condition B: Cooling Capacity: When indoor air is DB 27°C, WB 19.5°C, and inlet water temperature is 7°C Heating Capacity: When indoor air is 21°C, and inlet water temperature is 60°C
29