Fan Coil Unit
Floor Concealed Type
We aim to promote Korea's air conditioning technology worldwide
and grow into a globally competitive company through sustainable innovation.


Developed to adapt to changing environments, this latest product provides improved space utilization and a omfortable environment.
Features a low-noise, long-lasting, single-phase capacitor induction motor and a cross-flow fan.
For energy savings, installation of On/Off valves for each unit is recommended.Option
These control the flow in coordination with the unit’s operation preventing condensation issues during cooling, and reducing unnecessary preventing condensation of the circulation pump

Both central control and group control are available.Option
Central control can be achieved through power line communication and S-485 communication
Group control of up to 16 units can be performed using a wired remote controller.
The use of UV lamps provides outstanding effects in terms of sterilization antibacterial properties odor removal, and addressing sick building syndrome.Option
Korean Patent Registration No. 10-1147406

| MODEL | A | B | C | D |
|---|---|---|---|---|
| SFC-S1TM | 1200 | 900 | 1 | 1 |
| SFC-S2TM | 1800(2000) | 700(800) | 2 | 2 |
| No. | DESCRIPTION | MAT'L | Q'TY | REMARK |
|---|---|---|---|---|
| 1 | WATER OUTLET | BS | 1 | PF 3/4"(20A) |
| 2 | WATER INLET | BS | 1 | PF 3/4"(20A) |
| 3 | AIR VENT | BS | 1 | PT 1/8"(Manual) |
| 4 | DRAIN PAN | GI | 1 | - |
| 5 | HEAT & COOLING COIL | CU-AL | 1 | SLIT FIN |
| 6 | FAN IMPLLER | ABS | C | SIROCCO FAN(Ø96) |
| 7 | FAN HOSING | GI | C | - |
| 8 | MOTOR | ASS'Y | D | 1Ø 220V 60Hz |
| 9 | DRAIN CONNECTION | - | 1 | NIPPLE 1/2" (15A) |
| 10 | AIR FILTER | Vinyl Chloride | 1 | Submerged Type |
| Category | Specifications | SFC-S1TM | SFC-S2TM | |||
|---|---|---|---|---|---|---|
| Capacity | Capacity Conditions | A | B | A | B | |
| Cooling Capacity | W | 3,010 | 2,300 | 4,830 | 3,640 | |
| Kcal/h | 2,590 | 1,980 | 4,150 | 3,130 | ||
| Heating Capacity | W | 5,680 | 3,480 | 9,000 | 5,460 | |
| Kcal/h | 4,890 | 3,000 | 7,730 | 4,700 | ||
| Flow Rate | ℓ/min | 8.7 | 6.8 | 13.9 | 10.5 | |
| Head Loss | mAq | 0.8 | 0.5 | 3.5 | 2.0 | |
| Fan Blower | Type | Cross Flow Fan | ||||
| SIZE | mm | Ø96 X L715 | Ø96 X L715 | |||
| Airflow Volume | ㎥/min | 6.8 | 11 | |||
| Drive Type | Direct Drive Motor | |||||
| Quantity | EA | 1 | 2 | |||
| Motor | Type | AC Semi-Enclosed Type (4 poles, Class B insulation) | ||||
| Power Consumption | W | 20 | 45 | |||
| Quantity | EA | 1 | 2 | |||
| Heat Exchanger | Type | Integrated Multi-Pass Cross Finned Tube(Slit Fin) | ||||
| Pipe | Inlet | A | PF 3/4" (20A) | |||
| Outlet | A | PF 3/4" (20A) | ||||
| Drain | NIPPLE 1/2"(15A) | |||||
| External Material | Galvanized Steel Sheet, Powder Coating | |||||
| Air Volume Control | Direct Terminal Power Connection / rotary Switch (Optional) | |||||
| Power Supply | 단상 220V 60HZ | |||||
| AIR FILTER | Vinyl Chloride (Submerged) | |||||
| Product Weight | Kg | 23 | 48 | |||
| * Note | 1. Capacity Condition A - Cooling Capacity When indoor air is DB 27°C, WB 21°C, and inlet water temperature is 5°C Heating Capacity When indoor air is 18°C, and inlet water temperature is 80°C 2. Capacity Condition B - Cooling Capacity: When indoor air is DB 27°C, WB 19.5°C, and inlet water temperature is 7°C Heating Capacity: When indoor air is 21°C, and inlet water temperature is 60°C |
|||||