Page 49 - Fan Coil Unit
P. 49
Ceiling Concealed Type
Ceiling Cassette Type
7
Inspec�on
Hole
Concealed Type
Air Flow
Cold/Hot Water Flow
5 6 8 3 2 1 4 9
MODEL A B (Outlet) C (Hanger D (Motor) E (Fan) Part No DESCRIPTION MAT’L Q’TY REMARK
Position) 1 WATER OUTLET BS 1 PF 3/4" (20 A)
SFC-20CM 540 480 510 1 1 2 AIR VENT BS 1 PT 1/8" (Manual)
SFC-30CM 660 600 630 1 1 3 WATER INLET BS 1 PF 3/4" (20 A)
4 DRAIN PAN GI 1
SFC-40CM 780 720 750 1 2
5 AIR FILTER Vinyl Chloride 1 Submerged Type
SFC-60CM 1020 960 990 1 2 6 FAN & HOUSING ASS'Y E
7 MOTOR ASS'Y D Floor-Stand Type
SFC-80CM 1260 1200 1230 2 3
8 DRAIN CONNECTION 1 NIPPLE 3/4" (20 A)
SFC-120CM 1500 1440 1470 2 4 9 COIL ASS’Y CU-AL 1
Standard Specifications
Category Specifications SFC-20CM SFC-30CM SFC-40CM SFC-60CM SFC-80CM SFC-120CM
Capacity Conditions A B A B A B A B A B A B
Cooling W 2,790 2,120 3,700 2,810 5,360 4,050 7,220 5,490 10,440 7,870 13,610 10,260
Capacity Kcal/h 2,400 1,820 3,180 2,420 4,610 3,480 6,210 4,720 8,980 6,770 11,700 8,820
Capacity Heating W 5,640 3,470 7,780 4,770 10,990 6,710 14,330 8,760 21,240 12,950 23,640 14,340
Capacity Kcal/h 4,850 2,980 6,690 4,100 9,450 5,770 12,320 7,530 18,270 11,140 20,330 12,330
Flow Rate ℓ/min 8.1 6.0 10.7 8.0 15.4 11.5 20.8 15.7 30.0 22.4 39.1 29.3
Head Loss mAq 0.7 0.4 1.6 0.9 4.4 2.4 3.5 2.0 9.5 5.3 16.8 9.4 Stand Type
Type Double Suction Multi-Blade Type (SIROCCO FAN)
SIZE mm Ø145 X L165 Ø145 X L200 Ø145 X L165 Ø145 X L200 Ø145 X L200 Ø145 X L200
Airflow
Fan Blower m /min 5.7 8.5 11.3 17 22.6 34
3
Volume
Drive Direct Drive Motor
Quantity EA 1 1 2 2 3 4
Type AC Semi-Enclosed Type (6 poles, Class B insulation)
Motor
Quantity EA 1 1 1 1 2 2
Power Consumption W 45 55 70 85 55 + 85 85 X 2
Heat
Exchanger Type Integrated Multi-Pass Cross Finned Tube (Slit Fin)
Inlet A PF 3/4" (20 A)
Pipe Outlet A PF 3/4" (20 A)
Drain NIPPLE 1/2" (15 A)
External Material Galvanized Steel Sheet Facility Cultivation Type
Air Volume Control Strong, Medium, Weak 3-Stage Rotary Switch
Power Supply Single Phase 220 V 60 HZ
AIR FILTER Vinyl Chloride (Submerged)
Product Weight Kg 15 17 20 24 32 40
(Note) 1. Capacity Condition A: Cooling Capacity: When indoor air is DB 27°C, WB 21°C, and inlet water temperature is 5°C Heating Capacity: When indoor air is 18°C, and inlet water temperature is 80°C
2. Capacity Condition B: Cooling Capacity: When indoor air is DB 27°C, WB 19.5°C, and inlet water temperature is 7°C Heating Capacity: When indoor air is 21°C, and inlet water temperature is 60°C
49