Page 53 - Fan Coil Unit
P. 53
High-Pressure, Ceiling Concealed Type
Ceiling Cassette Type
Inspec�on
Hole
Concealed Type
5 6 1 2 3 9 7
Air Flow
Cold/Hot Water Flow
8 4
C (Hanger Part No DESCRIPTION MAT’L Q’TY REMARK
MODEL A B (Outlet) D (Motor) E (Fan)
Position) 1 WATER OUTLET BS 1 PF 3/4" (20 A)
SFC-H13 780 730 828 1 1 2 AIR VENT BS 1 PT 1/8" (Manual)
SFC-H17 1020 960 1068 1 2 3 WATER INLET BS 1 PF 3/4" (20 A)
4 DRAIN PAN GI 1
SFC-H21 1020 960 1068 1 2 5 AIR FILTER Vinyl Chloride 1 Submerged Type
SFC-H28 1200 1140 1248 2 3 6 FAN & HOUSING E Floor-Stand Type
7 MOTOR ASS'Y D
SFC-H31 1200 1140 1248 2 3
8 DRAIN CONNECTION 1 NIPPLE 1/2" (15 A)
SFC-H35 1440 1380 1488 2 4 9 COIL ASS’Y CU-AL 1
Standard Specifications
Category Specifications SFC-H13 SFC-H17 SFC-H21 SFC-H28 SFC-H31 SFC-H35
Capacity Conditions A B A B A B A B A B A B
Cooling W 5,380 4,050 7,230 5,490 10,510 7,970 12,620 9,480 14,060 10,640 17,730 13,430
Capacity Kcal/h 4,630 3,480 6,220 4,720 9,040 6,850 10,850 8,150 12,090 9,150 15,250 11,550
Capacity Heating W 11,070 6,710 14,330 8,760 21,220 13,020 25,450 15,470 28,440 17,380 31,420 21,860
Capacity Kcal/h 9,520 5,770 12,320 7,530 18,250 11,200 21,890 13,300 24,460 14,950 27,020 18,800
Flow Rate ℓ/min 15.5 11.5 20.8 15.7 30.2 22.8 36.2 27.1 40.4 30.5 50.9 38.5
Head Loss mAq 4.6 2.5 11.1 6.3 25.9 14.8 11.7 6.6 16.2 9.3 28.5 16.3 Stand Type
Type Double Suction Multi-Blade Type (SIROCCO FAN)
SIZE mm Ø192 X L170 Ø192 X L200 Ø192 X L200 Ø192 X L170 Ø192 X L200 Ø192 X L200
Airflow m /min 13 17 21 28 31 35
3
Fan Volume
Blower Drive Direct Drive Motor
External Static mmAq 5
Pressure (ESP)
Quantity EA 1 2 2 3 3 4
Type AC Semi-Enclosed Type (6 poles, Class B insulation)
Motor
Quantity EA 1 1 1 2 2 2
Power Consumption W 150 195 205 300 315 340
Heat
Exchanger Type Integrated Multi-Pass Cross Finned Tube (Slit Fin)
Inlet A PF 3/4" (20 A)
Pipe Outlet A PF 3/4" (20 A) Facility Cultivation Type
Drain NIPPLE 1/2" (15 A)
External Material Galvanized Steel Sheet
Air Volume Control Strong, Medium, Weak 3-Stage Rotary Switch
Power Supply Single Phase 220 V 60 HZ
AIR FILTER Vinyl Chloride (Submerged)
Product Weight Kg 30 34 36 40 42 46
(Note) 1. Capacity Condition A: Cooling Capacity: When indoor air is DB 27°C, WB 21°C, and inlet water temperature is 5°C Heating Capacity: When indoor air is 18°C, and inlet water temperature is 80°C
2. Capacity Condition B: Cooling Capacity: When indoor air is DB 27°C, WB 19.5°C, and inlet water temperature is 7°C Heating Capacity: When indoor air is 21°C, and inlet water temperature is 60°C
53