Page 55 - Fan Coil Unit
P. 55
High-Capacity, High-Pressure, Ceiling Concealed Type
Ceiling Cassette Type
Inspec�on
Hole F
5 6 1 2 3 8
Concealed Type
Air Flow
Cold/Hot Water Flow
7 4
MODEL A B (Outlet) C (Hanger D E F H Part No DESCRIPTION MAT’L Q’TY REMARK
Position) 1 WATER OUTLET BS 1 PF 3/4" (20 A)
SFC-H40 1150 940 1195 700 2 550 400 2 AIR VENT BS 1 PT 1/8" (Manual)
SFC-H45 1250 1040 1295 700 2 550 400 3 WATER INLET BS 1 PF 3/4" (20 A)
4 DRAIN PAN GI 1
SFC-H50 1450 1240 1495 700 2 550 400
5 AIR FILTER Vinyl Chloride 1 Submerged
SFC-H55 1580 1370 1695 700 2 550 400 6 FAN & MOTOR ASS'Y E
7 DRAIN CONNECTION 1 NIPPLE 3/4" (20 A) Floor-Stand Type
SFC-H60 1595 1490 1640 1050 2 900 600
8 COIL ASS’Y CU-AL 1
Standard Specifications
Category Specifications SFC-H40 SFC-H45 SFC-H50 SFC-H55 SFC-H60
Capacity Conditions A B A B A B A B A B
Cooling W 19,100 14,830 20,450 15,450 23,940 18,260 26,910 20,440 39,500 29,770
Capacity Kcal/h 16,430 12,750 17,590 13,290 20,590 15,700 23,140 17,580 33,970 25,600
Capacity Heating W 35,140 21,280 39,160 24,420 46,730 28,720 49,770 30,470 62,840 38,380
Capacity Kcal/h 30,220 18,300 33,680 21,000 40,190 24,700 42,800 26,200 54,040 33,010
Flow Rate ℓ/min 54.8 38.4 58.7 44.3 68.7 52.3 77.2 58.6 113.3 73.3 Stand Type
Head Loss mAq 2.2 1.1 2.9 1.6 4.6 2.7 6.5 3.7 2.5 1.1
Type Double Suction Multi-Blade Type (SIROCCO FAN)
Airflow Volume m /min 40 45 50 55 60
3
Fan Blower Drive Direct Drive Motor
External Static mmAq 5 (Additional external static pressure is optional)
Pressure
Type AC Semi-Enclosed Type (6 poles, Class B insulation)
Motor
Quantity EA 2 2 2 2 2
Power Consumption W 550 580 680 720 900
Heat Exchanger Type Integrated Multi-Pass Cross Finned Tube (Slit Fin)
Inlet A Socket PT 1" (25 A) Soket PT 40A
Pipe Outlet A Socket PT 1" (25 A) Soket PT 40A
Drain NIPPLE 3/4" (20 A)
External Material Galvanized Steel Sheet Facility Cultivation Type
Air Volume Control Strong, Medium, Weak 3-Stage Rotary Switch
Power Supply Single Phase 220 V 60 HZ
AIR FILTER Vinyl Chloride (Submerged)
Product Weight Kg 54 57 62 64 80
(Note) 1. Capacity Condition A: Cooling Capacity: When indoor air is DB 27°C WB 21°C, and inlet water temperature is 5°C Heating Capacity: When indoor air is 18°C, and inlet water temperature is 80°C
2. Capacity Condition B: Cooling Capacity: When indoor air is DB 27°C, WB 19.5°C, and inlet water temperature is 7°C Heating Capacity: When indoor air is 21°C, and inlet water temperature is 60°C
55