Page 19 - Energy Recovery Ventilation
P. 19
Ductless
Heat Recovery Ventilation Unit | Small
PART
L
A NO. PART NAME MAT'L Q'TY DESCRIPTION Slim
1 CASING SGCC 1 -
3 2 ACCESS DOOR SGCC 1 -
3 FAN & MOTOR - 2 BLDC MOTOR
6
4 HEAT EXCHANGER PULP 1 Special Processed Pulp for
Heat Exchange
SA EA 5 PRE-FILTER - 2 Nonwoven Fabric
6 MEDIUM FILTER - 1 Synthetic Fiber
D W B 7 DUCT FLANGE ABS 2 F (SA, RA) Small
8 MD ABS 1 F (EA)
RA OA 9 BDD ABS 1 F (OA)
10 CONTROL BOX ABS 1 PCB Included
DIMENSIONS
MODEL W L H A B D F
10 4 5
SW-150LHJ 580 580 250 390 630 350 Ø125 Standard
SW-250LHJ 650 650 230 500 690 427 Ø150
SW-350LHJ 730 700 250 500 771 339 Ø150
ABS
7 2 1 9 8
Standard Specifications
Classification Unit SW-150LHJ SW-250LHJ SW-350LHJ ABS/BYPASS
Strong Medium Weak Strong Medium Weak Strong Medium Weak
Airflow Volume CMH
150 150 120 250 250 200 350 350 250
Power Consumption W 57 44 35 105 93 76 175 164 145
Static Pressure mmAq 10 7 10 7 12 10
Product Size (W × L × H) mm 580 × 580 × 250 650 × 650 × 230 730 × 700 × 250
Duct Diameter mm (Ø) 125 150
Noise* dB 45dB (A) or less
Power Supply - Ø1 / 220 V / 60 Hz Large Capacity
Heat Recovery Rate % Heating: 77 / Cooling: 69 Heating: 75 / Cooling: 65 Heating: 76 / Cooling: 68
Heat Exchanger - Square Plate Heat Exchanger
Air Volume Control Method - ON/OFF, 3-Stage Control
Filter - PRE FILTER, MEDIUM FILTER
Casing - Galvanized Steel Sheet, Color-Coated Steel Sheet (optional)
Exhaust Unit
Optional Specifications - Deodorizing, HEPA Filter, etc.
* The noise level indication is based on the installation and completion of finishing work on-site.
19 ENERGY RECOVERY VENTILATION