Page 23 - Energy Recovery Ventilation
P. 23
Ductless
Heat Recovery Ventilation Unit | High-Efficiency ABS
PART
L
NO. PART NAME MAT'L Q'TY DESCRIPTION
A Slim
10 1 CASING ABS 1 -
2 ACCESS DOOR ABS 1 -
3 3 FAN & MOTOR - 2 BLDC MOTOR
Special Processed Pulp for
4 HEAT EXCHANGER PULP 1
Heat Exchange
SA EA 5 PRE-FILTER - 2 Nonwoven Fabric
6 MEDIUM FILTER - 1 Synthetic Fiber
D B W 7 DUCT FLANGE ABS 2 F (SA, RA) Small
8 MD ABS 1 F (EA)
RA OA 9 BDD ABS 1 F (OA)
2 10 CONTROL BOX ABS 1 PCB Included
DIMENSIONS
MODEL W L H A B D F
4 5 6
SW-150SCJ 529 493 220 449 485 220 Ø125 Standard
SW-200SCJ 602 630 250 582 552 254 Ø150
H
ABS
7 1 9 8
Standard Specifications
Classification Unit SW-150SCJ SW-200SCJ ABS/BYPASS
Strong Medium Weak Strong Medium Weak
Airflow Volume CMH
150 150 120 200 200 160
Power Consumption W 65 52 48 90 80 65
Static Pressure mmAq 10 7 10 7
Product Size (W × L × H) mm 529 × 493 × 220 602 × 630 × 250
Duct Diameter mm (Ø) 125 150
Noise* dB 45dB (A) or less
Power Supply - Ø1 / 220 V / 60 Hz Large-Capacity
Heat Recovery Rate % Heating: 70 / Cooling: 45 Heating: 70 / Cooling: 45
Heat Exchanger - Square Plate Heat Exchanger
Air Volume Control Method - ON/OFF, Three-Stage Control
Filter - PRE FILTER, MEDIUM FILTER
Casing - ABS
Exhaust Unit
Optional Specifications - Antibacterial, Deodorizing, HEPA Filter, etc.
* The noise level indication is based on the installation and completion of finishing work on-site.
23 ENERGY RECOVERY VENTILATION