Page 21 - Energy Recovery Ventilation
P. 21
Ductless
Heat Recovery Ventilation Unit | Standard
PART
L
NO. PART NAME MAT'L Q'TY DESCRIPTION
A Slim
1 CASING SGCC 1 -
9 2 ACCESS DOOR SGCC 1 -
3 FAN & MOTOR - 2 BLDC MOTOR
Special Processed Pulp for
OA RA 4 HEAT EXCHANGER PULP 1 SET Heat Exchange
5 PRE-FILTER - 2 SETS Nonwoven Fabric
D W B 6 MEDIUM FILTER - 1 SET Synthetic Fiber
7 DUCT FLANGE ABS 2 F (SA, RA) Small
EA SA 8 MD - 1 F (EA)
9 BDD - 1 F (OA)
8 10 CONTROL BOX SGCC 1 PCB Included
DIMENSIONS
Inspec�on Hole MODEL W L H A B D F
600 × 600
SW-500SHJ 745 900 430 758 787 387 Ø200 Standard
SW-800SHJ 1,200 1,200 450 1,078 1,242 500 Ø250
SW-1000SHJ 1,200 1,200 450 1,078 1,242 500 Ø250
3 2 5 4 6 1 7
H
10 ABS
Standard Specifications
Classification Unit SW-500SHJ SW-800SHJ SW-1000SHJ ABS/BYPASS
Strong Medium Weak Strong Medium Weak Strong Medium Weak
Airflow Volume CMH
500 500 400 800 800 700 1,000 1,000 800
Power Consumption W 240 191 180 420 248 214 500 413 375
Static Pressure mmAq 12 10 12 10 12 10
Product Size (W × L × H) mm 745 × 900 × 430 1,200 × 1,200 × 450 1,200 × 1,200 × 450
Duct Diameter mm (Ø) 200 250 250
Noise* dB 45dB (A) or less 50dB (A) or less 50dB (A) or less
Power Supply - Ø1 / 220 V / 60 Hz Large Capacity
Heat Recovery Rate % Heating: 78 / Cooling: 69 Heating: 75 / Cooling: 65 Heating: 75 / Cooling: 62
Heat Exchanger - Square Plate Heat Exchanger
Air Volume Control Method - ON/OFF, 3-Stage Control
Filter - PRE FILTER, MEDIUM FILTER
Casing - Galvanized Steel Sheet, Color-Coated Steel Sheet (optional)
Exhaust Unit
Optional Specifications - Antibacterial, Deodorizing, HEPA Filter, Photocatalyst Unit, etc.
* The noise level indication is based on the installation and completion of finishing work on-site.
21 ENERGY RECOVERY VENTILATION